Kipi Calculator CIRCUIT LOAD PLANNER by Kipi Calculator
🌐 Español

Circuit Load Calculator

    What needs power?

    Count the everyday stuff first — outlets and lights.

    General outlets Bedrooms, living areas, hallways (120V)
    Light fixtures Ceiling lights, cans, vanity bars

    Rule of thumb: up to 10 outlets per 15A circuit, 12 fixtures per lighting circuit.

    Kitchen, baths & big stuff

    These get dedicated circuits — code says so.

    Kitchen counter outlets Needs 2 dedicated 20A circuits if any
    Bathrooms 1 dedicated 20A circuit each
    240V appliances Range, dryer, water heater, AC (2 spaces each)

    Your circuit plan

    You need

    –

    General 15A
    –
    Kitchen 20A
    –
    Bath 20A
    –
    Lighting 15A
    –
    240V circuits
    –
    Est. wire
    –

      💡 Pro field tips

        🧰 Tools you'll need

        Tap to check off as you load up.

        Est. project cost (optional)

        File this estimate under a job name or PO to track what to order. Leave blank to file under "General".

        Size a breaker for one load

        Know the watts of one appliance or tool? Get its amps and a planning breaker size.

        Load From the appliance label or manual watts
        Voltage 120V for outlets, 240V for big appliances
        Assumptions & limits: Circuit and load estimates are for planning only. Breaker sizing, panel capacity, and all electrical work must follow the National Electrical Code (NEC) and local rules — when in doubt, hire a licensed electrician.

        How the math works

        This calculator does not size breakers from watts in the planner — it counts how many circuits a job needs, the way an electrician lays out a panel before any wire is pulled. You count the outlets, fixtures, bathrooms and big appliances; the tool turns those counts into circuits, panel spaces, and a cable estimate. For one single load, the breaker sizer under the planner (just above this section) works from watts instead.

        Step 1: General outlets — 1 circuit per 10

        General circuits = your outlet count ÷ 10, rounded up. 25 outlets ÷ 10 = 2.5, so 3 general 15A circuits.

        Step 2: Kitchens get 2 dedicated circuits

        If the job has any kitchen counter outlets, the count adds 2 dedicated 20A circuits — the code minimum for countertop appliances. No kitchen outlets, no added circuits.

        Step 3: One circuit per bathroom

        Each bathroom adds 1 dedicated 20A circuit.

        Step 4: Lighting — 1 circuit per 12 fixtures

        Lighting circuits = fixtures ÷ 12, rounded up, at 15A. 24 fixtures ÷ 12 = exactly 2 lighting circuits.

        Step 5: 240V appliances take 2 panel spaces

        Each 240V appliance (range, dryer, water heater) counts as 1 circuit but 2 spaces in the panel, because its breaker is a double-pole breaker.

        Step 6: Cable estimate

        The tool figures about 40 ft of cable per circuit, and rounds up to full 250-ft rolls.

        Step 7: Sizing a breaker for one load

        The breaker sizer under the planner works from a single load. The formula is Amps = Watts ÷ Volts: a 1,500-watt space heater on 120 volts draws 1,500 ÷ 120 = 12.5 amps. If the load runs 3+ hours at a time — a continuous load, like a space heater or an EV charger — code figures it at 125%: 12.5 × 1.25 = 15.63 amps. Then take the next standard breaker size up: 20A. Standard sizes run 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100. And the breaker protects the wire, so the wire must match the breaker — 14-gauge copper minimum on a 15A breaker, 12-gauge on a 20A.

        Worked example

        25 outlets, 24 light fixtures, kitchen counter outlets, 2 bathrooms, 1 dryer (240V): general 3 + kitchen 2 + bath 2 + lighting 2 + 240V 1 = 10 circuits, taking 11 panel spaces, with about 400 ft of cable (2 rolls).

        Planning estimates only — breaker sizing, panel capacity and all electrical work must follow the NEC and local rules; when in doubt, hire a licensed electrician.

        Most Asked Questions

        How many general circuits do I need for 25 outlets?

        3 general circuits. The calculator allows 10 general outlets per 15A circuit and rounds up: 25 ÷ 10 = 2.5, so 3 circuits. It is a planning count — size for the realistic worst case on each circuit, not the typical Tuesday.

        How many kitchen circuits does the calculator plan?

        2 dedicated 20A circuits, as soon as any counter outlets are entered. Kitchen counter outlets trigger the code-minimum pair of dedicated small-appliance circuits. Enter no counter outlets and the kitchen count is 0 — the two circuits exist because counters are where the heavy small appliances gather.

        How many circuits does each bathroom get?

        1 dedicated 20A circuit per bathroom. Enter 2 bathrooms and the plan adds 2 bathroom circuits. Bathrooms get their own dedicated circuits — code, not opinion — because hair dryers and heaters are big loads in a wet room.

        How are lighting circuits counted?

        1 circuit for every 12 light fixtures, rounded up. 25 fixtures ÷ 12 = 2.08, so the plan calls for 3 lighting circuits. Like the outlet count, it is an exact planning count from the numbers you enter — no hidden extra circuits are added.

        How much panel space does a 240V appliance take?

        2 panel spaces for each 240V appliance — while counting as 1 circuit. A dryer or range breaker is a double-pole breaker, so it eats two slots. The results keep the two numbers separate: total circuits for the plan, and total panel spaces so you can see whether the panel itself is big enough — over 40 spaces, the calculator flags that you may need a subpanel.

        How much cable does the calculator estimate?

        About 40 ft of cable per circuit, rolled up into 250-ft rolls. A 5-circuit plan figures roughly 200 ft of cable, which is 1 roll. It is a rough-in planning estimate — real runs depend on where the panel sits and how the walls route, so measure your actual paths before you buy.

        How do I size a breaker for one appliance?

        Use the breaker sizer under the planner: amps = watts ÷ volts. A 1,500 W space heater on 120 V draws 12.5 A. Because it runs for hours, it counts as a continuous load — multiply by 1.25 (15.63 A) and take the next standard size up: a 20A breaker. It is a planning figure only — confirm the final breaker and wire against NEC ampacity tables and local code with a licensed electrician.