15-Inch Pipe Slope Over 125 Feet
A 15-inch sewer or drain line runs at a 0.15% minimum slope. Over a 125-foot run that is 0.19 feet of fall — 2.25 inches (2 1/4″). If your upstream invert is 100.00 ft, the downstream invert lands at 99.81 ft.
Fall table — 15-inch pipe over 125 feet
| Distance from start | Fall so far | Fall (inches) | Invert (if start = 100.00) |
|---|---|---|---|
| 25 ft | 0.04 ft | 7/16 in | 99.96 ft |
| 50 ft | 0.07 ft | 7/8 in | 99.92 ft |
| 75 ft | 0.11 ft | 1 3/8 in | 99.89 ft |
| 100 ft | 0.15 ft | 1 13/16 in | 99.85 ft |
| 125 ft (end) | 0.19 ft | 2 1/4 in | 99.81 ft |
How it is figured
Slope × distance: 0.15% means the pipe drops 0.02 inches for every foot it runs (0.18″ every 10 ft, or 0.01 ft in rod tenths). Over 125 ft: 125 × 0.02″ = 2.25″ = 0.19 ft of fall.
0.15% is the standard minimum for 15-inch pipe — flat enough to keep solids moving without outrunning the water. Run it flatter and the line silts up; much steeper and water can outrun solids on long drops. Always confirm local code — some jurisdictions want more slope on 15-inch lines.
Figure a different run or a custom slope with the free storm drain calculator or the sewer line calculator.
Keep figuring
15″ over 75 ft · 15″ over 50 ft · 15″ over 25 ft · Storm drain calculator · Sewer line calculator · All charts & tables
Common questions
How much fall does a 15-inch pipe need over 125 feet?
At the standard 0.15% minimum slope, a 15-inch pipe falls 0.19 ft (2.25 in.) over 125 ft — 0.18 in. of fall every 10 ft.
What is the minimum slope for 15-inch pipe?
0.15% — that is 0.02 inches of fall per foot of run. It is the widely used minimum for 15-inch sewer and drain pipe; local code can require more.
How do I check the slope with a grade rod?
Grades are read in tenths of a foot. This run drops 0.01 ft every 10 ft, so each 10-foot station should read 0.01 ft lower than the last. String from invert to invert and check the rod at each station against the table above.