Wire Size Calculator

    What's the load?

    Amps and one-way distance — the formula doubles the distance for the round trip.

    Check the nameplate — or watts ÷ volts.

    Panel to the load, one direction only.

    What voltage?

    Higher voltage means less drop over the same run.

    Your wire size

    Use this copper wire

    –

    Voltage drop
    –
    Load
    –
    Distance (one-way)
    –
    Breaker for planning — load × 1.25
    –
    Wire needed
    –
    Copper K factor
    –

      💡 Pro field tips

        🧰 Tools you'll need

        Tap to check off as you load up.

        Est. project cost (optional)

        File this estimate under a job name or PO to track what to order. Leave blank to file under "General".

        Assumptions & limits: The right wire size depends on the load, the length of the run, voltage drop, insulation rating, and NEC ampacity tables. The breaker figure is for planning only (load × 1.25), not a code ruling — confirm the final wire and breaker sizes against the NEC ampacity tables and local code with a licensed electrician before installing.

        How the math works

        Wire has resistance, and resistance steals voltage. Push electricity through a long, thin wire and some of the voltage is lost as heat before it ever reaches the tool or light at the far end. Lose too much and motors run hot, lights dim, and equipment wears out early. Electricians keep voltage drop under 3%, and this calculator uses the standard voltage-drop formula to find the smallest wire gauge that stays under that limit for your amps and distance.

        Step 1: The voltage drop formula

        The formula is VD% = (2 × K × Amps × Length ÷ CM) ÷ Volts × 100. Here is what each piece means in plain words. K is the resistance of the wire metal — 12.9 for copper, 21.2 for aluminum (aluminum resists more, so it drops more voltage). Amps is the current the circuit carries. Length is the one-way distance in feet. CM is the wire's cross-section in circular mils — a bigger number means a fatter wire with less resistance. Volts is the circuit voltage.

        Step 2: Why the "2" is in the formula

        Electricity makes a round trip: out to the load on the hot wire and back on the neutral. The "2 ×" accounts for both legs of the journey. This is the most common DIY mistake in voltage drop math — people measure the distance to the shed (say, 100 feet) and forget the current travels 200 feet of wire total. Always use one-way distance and let the formula double it.

        Step 3: Testing gauges against the 3% limit

        The calculator starts with the thinnest wire allowed for your breaker and plugs its CM value into the formula. If the drop exceeds 3%, it steps up to the next fatter gauge and tries again. Thicker wire has a bigger CM number, which shrinks the result. It keeps going until the drop lands under 3% — that gauge is your answer. This is why long runs need surprisingly fat wire: a 20-amp circuit that is fine on 12-gauge at 30 feet may need 8-gauge at 150 feet.

        Step 4: Why 3% is the magic number

        The 3% guideline comes from equipment ratings. Most appliances are designed to run within about 5% of their rated voltage, and the wiring inside your house already eats some of that budget. Keeping the long run under 3% leaves headroom so the voltage at the outlet stays in the safe zone. Motors are the most sensitive — chronic undervoltage makes them draw extra current and burn out years early.

        Worked example

        A 20-amp, 120-volt circuit runs 100 feet to a shed, using copper wire. Try 12-gauge (CM = 6,530): VD% = (2 × 12.9 × 20 × 100 ÷ 6,530) ÷ 120 × 100 = 6.6% — too much. Step up to 10-gauge (CM = 10,380): (2 × 12.9 × 20 × 100 ÷ 10,380) ÷ 120 × 100 = 4.1% — still over. Step up to 8-gauge (CM = 16,510): 2.6% — under 3%, so 8-gauge copper is the answer. Upsizing for voltage drop changes the wire, not the load — the same 20-amp load just arrives at full voltage.

        Most Asked Questions

        What size wire do I need for a 20-amp, 120-volt circuit running 100 ft to a shed?

        8 AWG copper. The calculator tests each gauge against the 3% voltage-drop limit: 12 AWG drops 6.6% — too much; 10 AWG drops 4.1% — still over; 8 AWG lands at 2.6%, under the limit. Long runs need surprisingly fat wire, even when the load itself is ordinary.

        What wire does a lighter load need — say 12 amps at 80 ft on 120 volts?

        10 AWG copper, at a 1.99% drop. At that load and distance 14 AWG drops about 5.02% and 12 AWG about 3.16% — both over the 3% target — so the calculator steps up to 10 AWG. Shorter runs are the opposite story: the same load near the panel stays on much thinner wire.

        Why is 3% the voltage-drop limit?

        Because equipment is built to run within about 5% of its rated voltage. The wiring inside the building already eats some of that budget, so keeping the long run under 3% leaves headroom at the outlet. Motors are the most sensitive — chronic undervoltage makes them draw extra current, run hot, and burn out years early.

        Do I enter the distance there, or there and back?

        Enter the one-way distance — the formula already doubles it. Current travels out on the hot wire and back on the neutral, so a 100 ft run is 200 ft of wire in the math. Doubling it yourself is the most common DIY voltage-drop mistake, and it buys wire a size too fat.

        What breaker size does the calculator show?

        A planning figure only: your load × 1.25, rounded up to a standard breaker size. A 12-amp load figures 12 × 1.25 = 15, so a 15A breaker for planning. Treat it exactly that way — a planning figure. Confirm the final breaker and wire against NEC ampacity tables and local code with a licensed electrician before anything is installed.

        Does this calculator figure aluminum wire?

        No — it figures copper only. Every gauge it tests uses copper's resistance value (K = 12.9). Aluminum resists more, so the same run in aluminum needs a fatter gauge than this calculator shows — if you are running aluminum, have an electrician size it.