10-Inch Pipe Slope Over 25 Feet
A 10-inch sewer or drain line runs at a 0.28% minimum slope. Over a 25-foot run that is 0.07 feet of fall — 0.84 inches (13/16″). If your upstream invert is 100.00 ft, the downstream invert lands at 99.93 ft.
Fall table — 10-inch pipe over 25 feet
| Distance from start | Fall so far | Fall (inches) | Invert (if start = 100.00) |
|---|---|---|---|
| 25 ft (end) | 0.07 ft | 13/16 in | 99.93 ft |
How it is figured
Slope × distance: 0.28% means the pipe drops 0.03 inches for every foot it runs (0.34″ every 10 ft, or 0.03 ft in rod tenths). Over 25 ft: 25 × 0.03″ = 0.84″ = 0.07 ft of fall.
0.28% is the standard minimum for 10-inch pipe — flat enough to keep solids moving without outrunning the water. Run it flatter and the line silts up; much steeper and water can outrun solids on long drops. Always confirm local code — some jurisdictions want more slope on 10-inch lines.
Figure a different run or a custom slope with the free storm drain calculator or the sewer line calculator.
Keep figuring
10″ over 100 ft · 10″ over 75 ft · 10″ over 50 ft · Storm drain calculator · Sewer line calculator · All charts & tables
Common questions
How much fall does a 10-inch pipe need over 25 feet?
At the standard 0.28% minimum slope, a 10-inch pipe falls 0.07 ft (0.84 in.) over 25 ft — 0.34 in. of fall every 10 ft.
What is the minimum slope for 10-inch pipe?
0.28% — that is 0.03 inches of fall per foot of run. It is the widely used minimum for 10-inch sewer and drain pipe; local code can require more.
How do I check the slope with a grade rod?
Grades are read in tenths of a foot. This run drops 0.03 ft every 10 ft, so each 10-foot station should read 0.03 ft lower than the last. String from invert to invert and check the rod at each station against the table above.